Vexve AM CTS
Characteristics
- Suitable for maintaining a constant supply water temperature in Hydronic floor heating and air-conditioning applications as well as various process applications, easy installation without special tools
- Delivery includes a control for a single heating circuit
- All settings can be made and read directly from the controls on the front panel of the unit
- Stepless temperature adjustment: 10 °C – 80 °C
- Valve turning direction and loop speed control
Properties
- All settings can be made and read directly from the controls on the front panel of the unit
- 18 VAC supply voltage (low-voltage equipment, installation does not require an electrician)
- The controller is integrated with the motor section (IP41)
- 2 sensor inputs, RJ11/RJ12
- Motor unit 24VAC / 140s / 90 ° / 5Nm / 3-point control
- Mechanical setting ensures that settings are maintained in the event of a power failure
Delivery content:
Motor unit / AMCTS-controller 24 VAC / 140s / 90-degrees / 5Nm
- IP41-protection class
- Manual switch and mechanical position indication on the front panel
External power supply, 230 VAC 50 Hz / 18 VAC, 300 mA
- 2,5-meter connection cable, DC plug connections directly to the motor part/controller
Supply water temperature sensor (NTC 2K2)
- 1-meter connection cable, RJ12-connector
- Pipe fastening ties
Connection adapters to valves
Vexve AM series and Termomix valves, as well as other standard four-point attachment valves (adapters available for several other valves).
This device meets the following environmental requirements and standards:
- Operating temperature 0 … +40 °C
- Storage temperature −20 … +60 °C
- Shipping temperature −20 … +60 °C
- Humidity 0–100 % RH, non-condensing conditions
- RoHs 2002/95/EC
- CE-mark 93/68/EEC
- EMC-directive 2004/108/EEC
- LVD- directive 2006/95/EC
- General requirements for household control devices EN 60730–1:2000
- Special requirements for temperature controllers EN 60730-2-9:2002