naval underground ball valves ,
free shaft, welding / welding, EN (DIN), DN 150-400, full bore

Materials

Body DN 150-350 : Steel, P235GH (1.0345)
DN 400 : Steel, P355 NL1 (1.0566)/ GP240GH (1.0619)
Ball DN 150-400 : Stainless steel, X5CrNi18-10 (1.4301)
Ball seal DN 150-400 : PTFE+C
Stem DN 150-400 : Stainless steel, X8CrNiS18-9 (1.4305)
Stem seal DN 150-400 : FPM
Top of stem DN 150-400 : Stainless steel, X5CrNi18-10 (1.4301)

Operation

We recommend angle gear operation for sizes DN 150 and larger.

Operating conditions

-20 °C – +200 °C
Below -20 °C contact manufacturer
Lowest allowed ambient temperature -40 °C

Leakage rate A (EN 12266-1)

Pressure-temperature diagram DN 10–500

Dimension

DN 150-400

DNPNProduct no.DD1D2D3D4H1H2H3LSkg
1502523469405150168.3273.076.135.04904063344004,562.0
2002523469505200219.1355.676.140.05254153275305105.0
2502523469605250273.0457.088.950.05804433315505143.0
3002523469705290323.9508.0114.350.06034403296865,6167.0
3502523469805340355.6610.0168.370.06805023507626,3308.0
4002523469905390406.0660.0178.090.072051635011007,1570.0

Product numbers and downloads

Product NoEANLVIRSKNRFMMDNPNKvPhotokg
234694051502562.0
2346950520025105.0
2346960525025143.0
2346970530025167.0
2346980535025308.0
2346990540025570.0

Technical documentation for the product

Certificates

EHP003-certificate
EHP003-certificate
Share file
Serbia EN488 2018
Serbia EN488 2018
Share file

Operation manuals

Ball valve kv values chart and pressure loss diagrams
Ball valve kv values chart and pressure loss diagrams
Share file
Naval underground ball valves, installation, operation and maintenance manual
Naval underground ball valves, installation, operation and maintenance manual
Share file
Underground ball valves, coupling dimensions
Underground ball valves, coupling dimensions
Share file
Vexve underground ball valves, installation, operation and maintenance manual
Vexve underground ball valves, installation, operation and maintenance manual
Share file